Laserfiche WebLink
A <br />` WESTERN AMERICA TANK TEISTING, INC. �t <br />3131 Fairhaven Drive V tmvm <br />Bakersfield, CA 93308 MAR 1' 4 1991 <br />(soy) 322-9827 <br />PERM !Td F VIC <br />ANNUAL 3 -STEP RED JACKET LEAK DETECTOR TEST <br />OWNER QUIK STOP #132 <br />LOCATION <br />Stockton, CA. DATE 02/25/91 <br />PRODUCT: <br />Regular, Unleaded, Premium Unleaded, Diesel <br />(Circle one) <br />NOTE: Use separate form for each Tank. <br />(1) <br />Running Pressure 24 (2) Shut -Off Pressure <br />25 <br />(3) <br />Amount of Product Released thru Bibcock to Zero <br />16 oz. <br />(4) <br />With Valve Open --Start STP - List Pressure 0 <br />P.S.I., <br />(5) <br />Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 18 P.S.I., <br />(6) <br />Turn STP Off - Let Pressure drop to zero thru Leak just <br />created - List <br />time for Gauge to Reach Zero min. 15 <br />sec., <br />(7) <br />Turn the STP back on - Keep Leak Rate at Bibcock - List <br />pressure <br />18 P.S.I. — Flow Rate at Nozzle Full <br />G.P.M., <br />(8) <br />Stop Leak with STP still on - Does Leak Detector reset <br />X yes no <br />If yes - How long to reset min N/A sec., <br />(9) <br />Turn STP off - List pressure 24 P.S.I., <br />(10) <br />Turn STP back on - List time to reach pressure rise <br />min. 5 sec. <br />(11) <br />List Pressure 25 P.S.I., <br />(12) <br />Open Nozzle and List Pressure 24 P.S.I. <br />SATISFACTORY LEAK DETECTOR X Yes No. <br />LEAK DETECTOR <br />Model Red Jacket , <br />Date Code & Serial 116030 <br />