Laserfiche WebLink
_c <br />^ fi V <br />_ <br />WESTERN AMERICA TANK TRSTING, INC <br />3131 Fairhaven Drive <br />Bakersfield, CA 93308 MAR 1 101 <br />(805) 322-9827 ENVIRONMENTAL HE T <br />PERMIT/SERVICES <br />ANNUAL 3 -STEP RED JACKET LEAK DETECTOR TEST <br />OWNER QUIK STOP *132 <br />LOCATION Stockton, CA. DATE 02/25/91 <br />PRODUCT: Regular, Unleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use separate form for each Tank. <br />(1) Running Pressure 23 , (2) Shut -Off Pressure 25 , <br />(3) Amount of Product Released thru Bibcock to Zero 3 oz. <br />(4) With Valve Open --Start STP - List Pressure 1 P.S.I., <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 12 P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br />time for Gauge to Reach Zero min. 15 sec., <br />(7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br />12 P.S.I. — Flow Rate at Nozzle 1.5 G.P.M., <br />(8) Stop Leak with STP still on - Does Leak Detector reset __K_yes' no <br />If yes - How long to reset min 20 sec., <br />(9) Turn STP off - List pressure 25 P.S.I., <br />(10) Turn STP back on - List time to reach pressure rise min. 5 sec. <br />(11) List Pressure 25 P.S.I., <br />(12) Open Nozzle and List Pressure 24 P.S.I. <br />SATISFACTORY LEAK DETECTOR X Yes <br />LEAK DETECTOR <br />Model 116-030 , <br />am <br />Date Code & Serial g 40790-2153 <br />