Laserfiche WebLink
c <br />WESTERN AMERICA TANK TESTING, INC.' <br />3131 Fairhaven Drive MAR 14t"0 <br />Bakersfield, CA 93308 ENVIRONMEENTAL HEALTH <br />(805) 322-9827 PERMIT/SERVICES <br />ANNUAL 3 -STEP tir JACKET LEAK DETECTOR TEST <br />OWNER QUIK STOP #132 <br />LOCATION Stockton. CA. DATE 02/25/91 <br />PRODUCT: Regular, Unleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use seRarate form for each Tank. <br />(1) Running Pressure 24 , (2) Shut -Off Pressure 25 , <br />(3) Amount of Product Released thru Bibcock to Zero 12 oz. <br />(4) With Valve Open --Start STP — List Pressure 0 P.S.I., <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 22 P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br />time for Gauge to Reach Zero min. 15 sec., <br />(7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br />22 P.S.I. - Flow Rate at Nozzle Full G. P.M. , <br />(8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br />If yes - How long to reset min N/A sec., <br />(9) Turn STP off — List pressure 24 P.S.I., <br />(10) Turn STP back on - List time to reach pressure rise min. 5 sec. <br />(11) List Pressure 24 P.S.I., <br />(12) Open Nozzle and List Pressure 24 P.S.I. <br />SATISFACTORY LEAK DETECTOR X Yes <br />WM <br />LEAK DETECTOR <br />Model • 116-030 2156 Date Code & Serial # 40790-2155 <br />