Laserfiche WebLink
0 <br />QUIK STOP MARKETS, INC, <br />MAILING: P.O. BOX 5745 FREMONT, CA 94537 <br />LOCATION: 4567 ENTERPRISE ST. FREMONT, CA 94538 <br />October 5, 1988 <br />Quik Stop Market #132 <br />3555 W. Hammer Lane <br />Stockton, Ca. 95209 <br />OVERFILL PROTECTION MONITORING SYSTEM <br />Filling Procedures <br />415/657-8500 <br />1. Metered Input The load of gasoline to be delivered to site and <br />roppe into the underground storage tank(s) will be metered at <br />the loading terminal and run through a meter as it is loaded <br />onto the truck. <br />2. Visual MonitoringPrior to actual delivery of product into the <br />underground tanks at the site, the liquid Ievel of the tanks will <br />be measured and recorded on the delivery ticket. The truck driver <br />will control the visual monitoNIINg d filling of the tanks. <br />3. Available Tank Capacity After the liquid level of the tanks has <br />been determined, the driver will check the special tank charts <br />provided to determine whether or not the product can be safely <br />delivered into the tank. The tank(s) to be filled will have an <br />available capacity of 103% of the load to be dropped or the total <br />load plus 200 gallons capacity, whichever is less as determined <br />by the storage tank visual monitoring. <br />