Laserfiche WebLink
TANK ANNULAR TESTING <br />Test Method By: • Manufacturer • Industry Standard Professional Engr. Other (see below) <br />Test Method Uses: Pressure • Vacuum Hydrostatic Other (see below) <br />Measuring Equipment Used: Vacuum Gauge (range 0 to 30 inches Hg) <br />rluer-rir%*inn Tank 114 Tank $? Tank #3 <br />Tank manufacturer <br />Xerxes <br />Xerxes <br />Xerxes <br />Tank material <br />FRP <br />FRP <br />FRP <br />Tank capacity (US gallons) <br />10,000 <br />10,000 <br />8,000 <br />Product stored <br />Gasoline - 87 <br />Gasoline - 89 <br />Gasoline - 91 <br />Is this a mufti -compartment tank? <br />No <br />No <br />No <br />Dry or Brine filled annular? <br />if brine filled, perform no vacuum testing) <br />Dry <br />Dry <br />Dry <br />Monitoring system show nominal annular? <br />Yes <br />Yes <br />Yes <br />Is water table above tank bottom? <br />Unknown <br />Unknown <br />Unknown <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Yes <br />Wait time for vacuum to stabilize (hr.min) <br />0:06 <br />0:04 <br />0:03 <br />Test start time <br />1:00 PM <br />12:45 PM <br />12:25 PM <br />Initial vacuum (inches Hg) <br />10 <br />10 <br />10 <br />Test end time <br />2:00 PM <br />1:45 PM <br />1:25 PM <br />Final vacuum (inches Hg) <br />10 <br />10 <br />10 <br />Test duration (hr:min) <br />1:00 <br />1:00 <br />1:00 <br />Change in vacuum (inches Hg) <br />0 <br />0 <br />0 <br />Pass/Fail threshold (inches Hg / hour) <br />2 <br />2 <br />2 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Comments: <br />2003 Walton Engineering, Inc. <br />