. Depth to Groundwater(Lower) 92 85 to 106 55 feet bgs <br /> Groundwater Flow Direction (Lower) East <br /> Groundwater Gradient(Lower) 0 031 fVft <br /> SVE QUARTERLY OPERATION AND PERFORMANCE <br /> Equipment Inventory Solleco 500 cfm thermal oxidizer procured and installed <br /> during December 2004 and January 2005 <br /> Extraction Wells VW-1, VW-3, VW-4, VW-8, VW-14, MW-2, MW-8, and <br /> MW-9 <br /> Operating Mode Operational <br /> Required Permits San Joaquin Valley Air Pollution Control District <br /> (Permit No N-5026-3-0) <br /> Influent GRO Conc End of Period T 29,000 milligrams per cubic meter(mgliri) <br /> Influent Benzene Conc End of Period 720 Mg/M3 <br /> Influent MTBE Conc End of Period 12 mg/m3 _ <br /> Average Flow Rate This Period 317 93 cfm <br /> Average Applied Vacuum This Period 227 31"wc <br /> HC Destroyed This Period (lab) 4,338 40 lbs <br /> • Cumulative HC Destroyed 13,963 40 lbs as GRO(mass from old and new SVE <br /> systems) <br /> Number of Shutdowns 2 <br /> DISCUSSION <br /> Upper Water Bearing Zone (Sand Zone 1 <br /> During the second quarter 2005 (June 21, 2005), free product was found in well VW-1 at a thickness of <br /> 1 3 feet, and 3 gallons of product/water mixture were manually bailed Approximately 7 gallons (VW-1) <br /> and 14 gallons (VW-4) of product/water mixture have been manually balled to date Product thickness <br /> measurements and volumes of liquid bailed are summarized in Table 1 <br /> At the time of the second quarter 2005 monitoring event, groundwater levels had decreased between 0 90 <br /> and 7 57 feet in wells VW-2, VW-3, and VW-5, and increased between 0 26 and 5 96 feet in wells MW-2, <br /> MW-8, MW-13, VW-1, and VW4 since the previous monitoring event (March 14, 2005) Depth-to-water <br /> measurements were normalized to mean sea level (MSL) and used to construct a groundwater elevation <br /> contour map (Figure 3) Wells that contained less than 1 foot of water are interpreted to be dry and are <br /> Indicated as "dry" on Figure 3 The groundwater levels in wells VW-1, VW-3, and VW-5 appeared <br /> anomalous and these wells were not used in contour construction Groundwater flow was generally to the <br /> south-southeast at a gradient of 0 118 ft/ft Groundwater flow in the upper water bearing zone has been to <br /> the south, south-southeast, and toward the southwest during previous quarters <br /> GRO, benzene, and MTBE were reported In wells MW-8, VW-2, and VW-3 GRO and benzene were also <br /> reported in wells MW-13 and VW-4, and MTBE was also reported in well VW-5 The highest <br /> concentrations of GRO (110,000 µg/L) and benzene (7,900 fig/L) were reported in well VW-4, and the <br /> highest concentration of MTBE (290 j_Eg/L) was reported in well MW-8 1,2-DCA was reported in wells <br /> MW-2 (2 3 µglL), MW-8 (210 µg/L), MW-13 (0 70 µg/L), VW-3 (100 pg/L), and VW4 (970 µg/L) EDB <br /> K 113P-Arco for URS\6100\Quarterly\2005\Arco_6100_2Q05 doc Sr" U5 <br />