San Joaquin County
<br /> Environmental Health Department
<br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232
<br /> Telephone: (209)468-3420 Fax:(209) 468-3433 Web:www.sjgov.org/ehd
<br /> Underground Storage Tank Program Inspection Report
<br /> Facility Name: Facility Address: Date:
<br /> ARCO 06080 85 E LOUISE AVE, LATHROP February 01, 2017
<br /> SUMMARY OF VIOLATIONS
<br /> (CLASS I, CLASS II, or MINOR-Notice to Comply)
<br /> Item# Remarks
<br /> 313 HSC 25290.1, 25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight.
<br /> Seepage was observed at the union/shear valves at under dispenser containments 1-2 and 7-8, indicating a leak in
<br /> the primary piping. All primary containment for the UST system must be tight. Immediately have a properly
<br /> licensed, trained, and certified contractor repair or replace the failed components.
<br /> This is a repeat violation, Class ll.
<br /> 316 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion (after Jul 2003).
<br /> Approximately one-half cup of liquid was observed in the 87-product submersible turbine pump (STP) sump,
<br /> approximately one quart of liquid was observed in the diesel STP sump, approximately one-half cup of liquid was
<br /> observed in the diesel fill sump, approximately one-half cup of liquid was observed in the 91-product STP sump, a
<br /> trace of liquid was observed in under dispenser containment(UDC) 1-2, approximately one-half cup of liquid was
<br /> observed in UDC 34, and approximately three cups of liquid were observed in the vent box. Secondary
<br /> containment shall be constructed to prevent any water intrusion into the system by precipitation, infiltration, or
<br /> surface runoff. Immediately remove this liquid, make a hazardous waste determination per Title 22 hazardous
<br /> waste regulations, and manage accordingly. Immediately contact a properly licensed, trained, and certified
<br /> contractor to address the water intrusion into the sumps, UDCs and vent box listed above.
<br /> The diesel secondary containment fill sump is not liquid and vapor tight. The gasket for the inner sump opening is
<br /> missing. Secondary containment shall be impervious to the liquid and vapor of the substance contained and
<br /> constructed to prevent structural weakening as a result of contact with any hazadous substances released from the
<br /> primary containment. This same violation was reported during the 2016 monitoirng system certification inspection
<br /> and still has not been corrected. Immediately contact a properly licensed, trained, and certified contractor to replace
<br /> the gasket for the inner sump opening of the diesel fill sump.
<br /> This is a repeat violation, Class Il.
<br /> Overall Inspection Comments:
<br /> An inspection checklist was provided to the facility clerk on the day of inspection (February 1, 2017). The
<br /> Environmental Health Department (EHD) has written the complete report which replaces the initial checklist.
<br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement
<br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting
<br /> paperwork, within 30 days of receiving the complete inspection report.
<br /> Communication in the 87-, 91-, and diesel- product submersible turbine pump (STP) sumps and fills sumps, and
<br /> communication in the under dispenser containments (UDC) of the vacuum-pressure-hydrostatic (VPH) system
<br /> were not tested during the inspection on February 1, 2017.
<br /> Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program
<br /> documents into the California Environmental Reporting System (CERS): UST Monitoring Site Plan, UST
<br /> Certification of Financial Responsibility, UST Response Plan, UST Letter from Chief Financial Officer (if
<br /> applicable), and the Owner Statement of Designated Operator Compliance. The UST Owner/Operator: Written
<br /> Agreement, if applicable, can be stored at the facility or uploaded into CERS. .
<br /> FA0003635 PR0231656 SCO01 02/01/20 '
<br /> EHD 23-01 Rev.09/22/16 Page 5 of 6 Underground Storage Tank Program,
<br />
|