Laserfiche WebLink
U � <br /> �fi 4 Fd <br /> Lancaster <br /> Laboratories Analysis Report <br /> 425 New Holland Pike PO Box 12425 Lancaster PA 17605-2425 717-656 230o Fax 717 656-2681•www lancasterlabs corn <br /> Page 7 of 7 <br /> Quality Control Summary <br /> Client Name ChevronTexaco Group Number 861384 <br /> Reported 08/11/03 at 11 35 PM <br /> Surrogate Quality Control <br /> Limits 59-139 <br /> Analysis Name EPA SW846/8260 {water} <br /> Batch number N032211AA <br /> Dzbromofluoromethane 1,2-Dichloroethane-d4 Toluene-d8 4-Bromofluorobenzene <br /> 4092148 99 91 92 90 <br /> Blank 102 93 92 90 <br /> LCS 99 93 95 99 <br /> MS 99 93 95 98 <br /> MSD 97 91 93 98 <br /> Limits 61-120 82-112 85-112 83-113 <br /> Analysis Name BTEX+MTBE by 8260B <br /> Batch number P032202AA <br /> Dxbromofluoromethane 1,2-Dichloroethane-d4 Toluene-ds 4-Bromofluorobenzene <br /> 4092147 102 98 92 90 <br /> 4092150 104 98 91 91 <br /> 4092151 102 96 92 92 <br /> 4092152 99 100 89 104 <br /> Blank 102 98 91 91 <br /> LCS 100 98 90 93 <br /> s 101 102 92 94 <br /> &— '–' <br /> SD 102 99 90 91 <br /> Limits 81-120 82-112 85-112 83-113 <br /> *-Outside ofspecification <br /> 10 <br /> (1) The result for one or both determinations was less than five times the LOQ <br /> (2) The background result was more than four times the spike added <br />