A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> UNITED#5447 1 1469 E HAMMER LN, STOCKTON August 11, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> OBSERVATION: Designated operator reports were not signed within the required time frame. <br /> -The 09/06/2019 designated operator report was signed by the owner/operator on 09/09/2019. <br /> REGULATORY GUIDANCE: Within 48 hours of the completion of the designated UST operator visual inspection, <br /> the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 48 <br /> hours of being provided a signed copy of the report, the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a minor violation. <br /> 307 CCR 2631(g), 2632(c) Monitoring system of the interstitial space of a double walled system not maintained. <br /> OBSERVATION: The 87 annular sensor failed to activate an audible and visual alarm when tested and, therefore, <br /> the tank is not monitored. <br /> REGULATION GUIDANCE: The interstitial space shall be monitored with a monitoring system connected to an <br /> audible and visual alarm system. <br /> CORRECTIVE ACTION: The sensor was replaced and retested during the inspection. A"UST Retrofit Verification <br /> with Inspector Already Onsite"form has been completed and provided to the operator and contractor. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failed to maintain a continuous monitoring system that activates an audible and <br /> visual alarm. <br /> OBSERVATION: The 91 and diesel STP sump sensor failed to activate an audible and visual alarm when tested to <br /> ensure continuous monitoring of the tank system. <br /> REGULATION GUIDANCE: All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The sensor was replaced and retested during the inspection. A"UST Retrofit Verification <br /> with Inspector Already Onsite"form has been completed and provided to the operator and contractor. <br /> This was corrected on site. <br /> This is a minor violation. <br /> FA0001570 PR0231126 SCO01 08/11/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />