Laserfiche WebLink
Appendix B <br />7150 Overfill Valve in Tank Shut off Level Worksheet <br />Important: This is meant to be supplemental worksheet and nota substitute to following the installation <br />manual instructions. All length measurements are in inches. Piease contact the Authority Having Jurisdic- <br />ticm (AHJ) and review local, state, and national codes to determine the regulatory requirements governing <br />shut-off capacity in your region, as well as take into account other considerations such as extreme tank tilt. <br />Take the following measurements with the valve in- <br />stalled in the tank <br />Distance from the 71 SO inlet tube flange to the can <br />lug In the 71 SO body (see figures), upper tube length. <br />Note: the Upper Tube Length must be at least 16" to in- <br />clude the protective bend In the tube. <br />(D)= <br />Distance from the 71 SO inlet tube flange to the top and <br />bottom of lower tube, valve length. <br />(W)= <br />(U) _ <br />Distance from the 7150 inlet tube flange to the bottom <br />of the tank. Note: If a tank bottom protector is present It <br />may be necessary to add this thickness to dimension <br />(OPW 6111 & 61 TP models add 0.6") <br />(8)= <br />From the tank calibration chart provided by tank manu- <br />facturer find the dipstick number M which corresponds <br />to the 100% volume. <br />(Y) _ <br />1. Tadetermineahut-offpercentagea <br />Subtract upper tube length (D) from distance to tank <br />bottom (8) <br />(X)=(8) -(D)-2"= <br />Using the tank calibration chart provided by the tank <br />manufacturer determine the tank capacity at the cal- <br />ulated (X) dimension and the 100% volume IYI tank <br />capacity. <br />(X) tank capacity in gallons = <br />IYI tank capacity in gallons <br />50%= (X) capacity / (Y) capacity x100 = <br />Now: The overfill valve must be Installed per AHJ require- <br />ments and all applicable local, state, and national codes. If <br />the overfill valve is set above the allowable shut-off percent- <br />age the overfill wive must be removed and replaced. For <br />reference 40 CFR part 280 Subpart B Section 280.20 pwrfill <br />valves should be set to a maximum of 959L <br />Appendix C <br />HOW TO LOCATE THE POSITION OF THE 7150 FOR COMPLETE SHUT-OFF AT A GIVEN TANK CAPACITY <br />Note: This Appendix only applies when AHl require- <br />ments call for complete shut-off at a given tank capacity. <br />See page 4 for standard measurements. <br />The length of the upper tube and the placement of the <br />7150 valve body determine the shutoff point The sat, <br />ple calculation below will provide for complete shut-off <br />at 95%. In all cases, the upper tube length must be a <br />minimum of 6-1/2' plus the length of the dser pipe. All <br />length measurements are in Inches. <br />INSTRUCTIONS <br />1. Find the tank capacity(in gallons) from the tank call- <br />bration chart provided by the tank manufacturer. <br />2. Calculate 95% of capacity. <br />3. Locate the 95%volume num bar onthe tankcalibra- <br />tion chart. <br />4. Find the dipstick number (X) which corresponds to <br />the 95% tank volume. And, find the dipstick number <br />(Y) which corresponds to the 100% volume. <br />S. Subtract the dipstick number (X)from the tank diam- <br />eter M to find the upper tube reference number (Z). <br />m-W=(n <br />6. Add 1.5" to (Z) to find the upper tube depth E <br />(Z)+15'=E <br />7. Is E less than 6-1/2'7 <br />NO Upper tube length is E plus the distance from the <br />top of the Face Seal Adaptor Installed on the riser <br />pipe to the Inside, top lip of the storage tank (A). <br />Upper Tube Length = E + (A) <br />For testable models only, ending In T: <br />Upper Tube Length - E + (A) -1-1l2" <br />YES Upper tube length is 6.1/2" plus the riser pipe <br />measurement (A). <br />Upper Tube Length = 6.1/2" + (A) <br />For testable models only, ending in "T <br />Upper Tuba R <br />Length = 6-i"+(A) - 1-1/2 <br />NOTE: You must find the actual tank capacity num- <br />ber that correlates to the 6-1/2" + (A) depth for the <br />station records. This number may also be used or <br />the purposes of calibrating an electronic tank level <br />system. <br />EXAMPLE <br />1. For an Owens-Corning Model G-3 Fiberglass' Tank <br />Calibration Chart: <br />Tank Capacity -10,000 gal. nominal 9,403 gal. <br />NOTE: Use actual capacity only <br />R,xr Rqp <br />seeFaw <br />SalAdaga <br />2. 95% of actual tank capacity = 0.95 x 9403 gal. _ <br />8933 gal. <br />3. The closest number which is less than 8933 gal. Is <br />8910 gal. Choosing the closest number less than <br />95% of actual ca patty ensures that complete <br />shutoff will occur when the tank Is no more than <br />9S% full. <br />4. The callbration chart reading of 8910 gal. mde- <br />sponds to a dipstick measurement of 82". <br />5. Dipstick number (X) = 82" <br />Tank diameter M = 92" <br />(Y)-(X)=(Z) (92"-82'=10") <br />(Z) =10" <br />6. (Z)+15'=E (10"+15'=1151 <br />E = 115" <br />7. Is 11.5" less than 6.1/2'7 <br />NO Measure the distance from the top of the FSA-400 <br />Face Seal Adaptor installed on the riser pipe to <br />the Inside, top lip of the storage tank and obtain <br />measurement (A). <br />Upper tube length = E+ (A) <br />For testable models only, ending <br />Upper Tube Length = E + IA) - 1-1 /2" <br />2. To determine lower tube distance from tank <br />bottom to bottom of cut: <br />Subtract valve length (W) from distance to tank <br />bottom (B) <br />W)=(B)-(W)= <br />Note. Lower tube clearance must meet tank manufac- <br />turer requirements and all AHJ, local, state, and national <br />codes. Typical clearance Is about 4". If lower tube clean, <br />ance is not met valve must be removed and adjusted to <br />meet these requirements. <br />3. To determine lower tube distance from tank <br />bottom to top of cut: <br />Subtract valve length (U) from distance to tank <br />bottom (8) <br />(T) _ (B) - (U) _ <br />Note: Lower tube distance from tank bottom to top of <br />cut must meet all AHJ, local, state, and national codes. <br />For reference per 40 LFR 63 subpart CCCCCC / NESHAP <br />the lower tube can be no more than 6" from the bottom <br />of the tank If lower tube distance is not met valve must <br />be removed and adjusted to meet these requirements. <br />4. To determine float alignment: <br />Looking Into upper tube (see figure) the float should be <br />aligned along the length of the tank Iffloatisnot <br />aligned properly adjustments need to be made. <br />View into drop tube from above <br />Appendix C (continued] <br />7150 Overfill Valve In Tank Cumulate Shut Off Level Worksheet <br />Important: This is meant to be supplemental worksheet and not a substitute to following the installation <br />manual instructions. All length measurements are in inches. Please contact the Authority Having Jurisdic- <br />tion (AHJ) and review local, state, and national codes to determine the regulatory requirements governing <br />shut-off capacity in your region, as well as take into account other considerations such as extreme tank tilt. <br />Take the following measurements with the valve in- <br />stalled in the tank: <br />Distance from the 71 SO Inlet tube flange to the cast <br />lug in the 71 SO body (see figures), upper tube length. <br />Note: the Upper Tube Length must beat least 16" to In- <br />clude the protective bend in the tube. <br />(D) _ <br />Distance from the 71 SO Inlet tube flange to the top and <br />bottom of lower tube, valve length. <br />(W)= <br />(U) _ <br />Distance from the 7150 Inlet tube flange to the bottom <br />of the tank Note: If a tank bottom protector is present it <br />may be necessary to add this thickness to dimension <br />(OPW 6111 & 61 TP models add 0.6") <br />(B)= <br />From the tank calibration chart provldad by tank manu- <br />facturer find the dipstick number M which corresponds <br />to the 100% volume. <br />(n= <br />1. To determine complete shut-off percentage: <br />Subtract upper tube length (D) from distance to tank <br />bottom (B) <br />(X)=(B)-(D)+ 1.5"= <br />Using the tank calibration chart provided by the tank <br />manufacturer determine the tank capacity at the cal- <br />culated (X) dimension and the 100% volume (Y) tank <br />capacity. <br />(X) tank capacity In gallons = <br />(Y) tank capacity In gallons - <br />Complete S0%= (X) capacity / (Y) capacity x100 = <br />(D) <br />Upper <br />Tube <br />IW) Valve <br />Length, <br />bottom <br />of cut <br />(B) <br />To Tank <br />m <br />Tank <br />(U) Valve <br />Chart <br />Length, <br />100% <br />topof <br />Volume <br />Dipstick <br />Note: The overfill valve must be installed per AHJ re- <br />quirements and all applicable local, state, and national <br />codes. If the overfill calve is set above the allowable <br />shut-off percentage the overfill valve must be removed <br />and replaced. <br />Note: -6 Appendix only applies to valves Installed per Appendix C. See Appendix B for the standard valve <br />installation tank shut off level worksheet <br />24 <br />