Laserfiche WebLink
FEBRUARY 11, 1991 <br />WESTERN METER SERVICE, INC <br />2735 TEEPEE DRIVE <br />STOCKTON, CA 95205 <br />ATTN: BURL DUBOSE <br />RE: 11919 LOWER SACRAMENTO ROAD; PRECISSI FLYING SERVICE <br />I HAVE REVIEWED THE UNDERGROUND STORAGE TANK (UGT) INSTALLATION <br />PLAN FOR THE ABOVE REFERENCED FACILITY AND FOUND THE FOLLOWING <br />DEFICIENCIES: <br />t5i41 1- NEED TO INDICATE HOW MANY AND .rtvam rr �Tr�_ n + TS WILL BE <br />by- INSTALLED. PAGE 5 INDICATES N FIBERGLASS UGST WILL BE <br />INSTALLED BUT SPEC SHEET (PAGE 1) INDICATES A POSITE TANK <br />WILL BE INSTALLED. ALSO, PAGE 7 INDICATES THERE WILL BE TWO <br />UGT BECAUSE IT SAYS 11 10,000 GAL. TANKS (2) SIDE BY SIDE ONE <br />GASOLINE". PAGE 28 ALSO SAYS °'... MONITORING DEVICE WILL BE <br />INSTALLED IN BOTH TANKS..". <br />0.2- NEED TO INDICATE THAT THE MSA CONTROL UNIT, AS WELL AS THE <br />\ \ LIQUID SENSORS, ARE U.L. LISTED. <br />3- WHICH FUEL WILL BE STORED IN THE TANK( )? AVIATION FUEL R <br />GASOLINE OR BOTH? <br />IF AV GAS IS TO BE STORED, IS GALVANIZED PIPING COMPATIBLE WITH <br />AV GAS? WHAT ABO THE UGT(S)? <br />5- IF TANKS AR COMPOSIT EY NEED TO INDICATE THAT THEY HAVE A <br />U.L. 1358 OR 746 LISTING, NOT JUST U.L. 58. <br />6- IF THE SINGLE WALL FILL PIPE IS NOT DESIGNED TO PREVENT <br />OVERFILL THEN IT MUST BE DOUBLE WALLED AND MONITORED <br />CONTINUOUSLY. <br />�\�\ PLEASE INDICATE ANY AND ALL PIPING RUNS ON SITE MAP, INCLUDING <br />THE VENT PIPING. <br />U`\ 8 THE ACTIVE FEES FOR 1991 STILL HAVE TO BE PAID. YOU PAID $50 <br />TOWARD THE ACTIVE FEES FOR 1990, HOWEVER, THE TANK WAS NOT <br />n� 0\V INSTALLED IN 1990 THEREFORE THE $50 WILL BE CREDITED TOWARD THE <br />$170 OWED FOR 1991, WHICH MEANS THAT $120 IS STILL DUE FOR <br />1991. <br />SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS LETTER, CONTACT KASEY <br />FOLEY AT (209) 468-3468. <br />