Laserfiche WebLink
f aA <br /> SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:Dwyer Manometer Equipment Resolution:+/-2% <br /> Tank# 1 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes x No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 5,000 <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Unknown <br /> Product Stored: Diesel <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Min <br /> starting test: <br /> Test Start Time: 9:35 <br /> Initial Reading(Rj): 7.67 <br /> Test End Time: 10:35 <br /> Final Reading(RF): 7.65 <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-RI): .02 <br /> Pass/Fail Threshold or Criteria: No less 1"drop <br /> Test Result: z Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fait ❑ Pass ❑Fail <br /> Was sensor removed for testing? x Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No [INA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and x Yes ❑No ❑NA ❑Yes 11 No 11 NA ❑Yes ❑No ❑NA ❑Yes ❑No El NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> tacf;n" frnlifnr ;n('Arles Titles 11 IzApt/nn')AIWOV6�t <br />