Laserfiche WebLink
SWRCB,January 2002 Pa Of <br /> N 0 V 1 70T4 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer El Industry Standard FE7E I <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure X Vacuum E-I'Hydrostatic <br /> 11 Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution:- V2"x-30"Hg. <br /> 4"' <br /> MIMES= <br /> Tank# 1 Tank# Tank# Tank# <br /> Is <br /> Test <br /> Exempt From Testing?' No <br /> Tank Capacity: 5K <br /> Tank Material: Jacketed DW Steel <br /> Tank Manufacturer: Trusco <br /> Product Stored: Fuel Oil <br /> Wait time between applying 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 1:35 <br /> Initial Reading(Rj): -7 Hg. <br /> Test End Time: 2:35 <br /> Final Reading(RF): -7 Hg. <br /> Test Duration: I Hour <br /> Change in Reading(RF-Ri): 0 Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />