Laserfiche WebLink
SWRCB,January 2002 Page-2_of_2 <br /> 6. PIPING SUMEP TESTING <br /> Test Method Developed By: ❑Sump Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Spec6) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic' <br /> ❑Other(Spec) <br /> Test Equipment Used:INCON SUMP TESTER Equipment Resolution:+I-0.002" <br /> Sump#LTC Sump# Sump# Sump# <br /> Sump Diameter: 48" <br /> Sump Depth: 53.50" <br /> Sump Material: FIBERGLASS <br /> Height from Tank Top to Top of 33" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 20„ <br /> Electrical Penetration: <br /> Condition of sump prior to testing: DRY <br /> Portion of Sump Tested' ABOVE <br /> PENETRATIONS <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes [:]No ®NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No [INA <br /> product and water)?* <br /> Turbine shutdown response time NIA <br /> Is system programmed for fail-safe ❑ ®NA ❑Yes ❑NA ❑yes <br /> shutdown?* <br /> E]Yes No ❑No ❑No ❑NA [_1 Yes El No ❑NA <br /> Was fail-safe verified to be Cj Yes ❑No ®NA ❑Yes ❑No ❑NA []Yes ❑No ❑NA [:]Yes ❑No [:INA <br /> o erational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 10 MIN <br /> test: <br /> Test Start Time: 10:06 AM <br /> Initial Reading(RI): 4.9196" <br /> Test End Time: 10:21 AM <br /> Final Reading(RF): 4.9193" <br /> Test Duration: 15 MIN <br /> Change in Reading(RF-RI): -0.0003" <br /> Pass/Fail Threshold or Criteria: +l-0.002" +/-0.00211 +l-0.002" +l-0.002" <br /> Test Result: 'Rpass 0yFat1 ❑;Pass ❑TaIL' ❑,Pass ❑Fail. LSI, ss C�Fai1' <br /> Was sensor removed for testing? ®Yes ❑No ❑NA [:]Yes ❑No [INA ❑Yes [:]No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and SNA ®yes [:]No ❑NA ❑Yes ❑ ❑ ❑Y <br /> verified functional after testing? ®Yes ❑No No NA es ❑No ❑NA <br /> Comments—(include fn ormafion on repairs made prior to testin , and recommended follow- yr ailed tests) <br /> ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS <br /> I If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the;questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />