SWRCB, January 2002 <br />4. TANK ANNULAR TESTING <br />Ll <br />Page _2_ of _8_ <br />Test Method Developed By: ❑ Tank Manufacturer ® Industry Standard F-1 Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ® Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: 0 — 30" VACUUM GAUGES <br />Equipment Resolution: + / - 0.002" <br />Tank # 87(1) <br />Tank # 87(2) <br />Tank # 91(3) <br />Tank # <br />Is Tank Exempt From Testing?' <br />❑ Yes ® No <br />❑ Yes ® No <br />❑ Yes ® No <br />❑ Yes ❑ No <br />Tank Capacity: <br />12000 <br />12000 <br />10000 <br />Tank Material: <br />FIBERGLASS / <br />STEEL <br />FIBERGLASS / <br />STEEL <br />FIBERGLASS / <br />STEEL <br />Tank Manufacturer: <br />MODERN WELDING <br />MODERN WELDING <br />MODERN WELDING <br />Product Stored: <br />87 <br />87 <br />91 <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time: <br />9:00 AM <br />9:00 AM <br />9:00 AM <br />Initial Reading (RI): <br />-10" <br />-10" <br />-10" <br />Test End Time: <br />10:00 AM <br />10:00 AM <br />10:00 AM <br />Final Reading (RF): <br />-10" <br />-10" <br />-10" <br />Test Duration: <br />1 HR <br />1 HR <br />I HR <br />Change in Reading (RF -RI): <br />0" <br />0" <br />0" <br />Pass/Fail Threshold or Criteria: <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />t«na&s <br />;�j <br />Fail`"` <br />PSS Fail®Pass <br />❑ EaI <br />❑'I�aS ©,1 <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA <br />® Yes [:]No ❑NA <br />® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testi ? <br />®Yes El No ❑ NA <br />®Yes ❑ No [:1 NA <br />®Yes ❑ No ❑ NA <br />❑Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. (California Code of Regulations, Title 23, Section 2637(a)(6)) <br />