Laserfiche WebLink
SWRCB, January 2002 0 <br />Page _7_ of —8- <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: VISUAL <br />Equipment Resolution: TAPE MEASURE <br />Spill Box # 87(1) FILL <br />Spill Box # 87(1) <br />Spill Box # 87(2) FILL <br />Spill Box # 87(2) <br />VAPOR <br />VAPOR <br />Bucket Diameter: <br />16" <br />16" <br />16" <br />16" <br />Bucket Depth: <br />15.25" <br />16.50" <br />15.75" <br />16.25" <br />Wait time between applying <br />pressure/vacuum/water and <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />starting test: <br />Test Start Time: <br />10:00 AM <br />10:00 AM <br />10:00 AM <br />10:00 AM <br />Initial Reading (Ri): <br />14" <br />15.25" <br />14" <br />15.25" <br />Test End Time: <br />11:00 AM <br />11:00 AM <br />11:00 AM <br />11:00 AM <br />Final Reading (RF): <br />14" <br />15.25" <br />14" <br />15.25" <br />Test Duration: <br />1 HR <br />1 HR <br />1 HR <br />1 HR <br />Change in Reading (RF -RI): <br />0" <br />0" <br />0" <br />0" <br />Pass/Fail Threshold or <br />Criteria: <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />Comments — (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />