fi. UNDER-DISPENSER CONTAINIMENT fTMQ TESTTNG <br /> Test Method Developed By: ❑UDC Manu urer Ind Standard ❑Professional Engineer <br /> ®Other(Spec) <br /> Test Method Used: ❑Pressure Q Vacuum Z1 Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002 Inches <br /> A <br /> C# 7/8 UDC# 11/12 UDC# UDC# <br /> C Manufacturer: Bravo Bravo <br /> UDC Material: Steel Steel <br /> UTC Depth: 12" 12" rl F _,,. _ <br /> d:D <br /> Height from UDC Bottom to Top Located on Bottom Located on Bottom <br /> of Higest est Pi in Penetration: <br /> Height from UDC Bottom to Located on Bottom Located on Bottom <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good ENS I ONMENTALS LT <br /> testin <br /> Portion.of UDC Tested 2"Above Piping 2"Above Piping <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both NIA NIA <br /> product and water)?. <br /> Turbine shutdown res ones time NIA NIA NIA NIA <br /> Is system programmed for fail- ®Yes ❑Na 0 NA ❑Yes ❑No ®NA ❑Yes O No DNA ❑Yes ❑No ❑NA <br /> safe shutdown7* <br /> Was fail-safe verified to be ❑Yes ❑No ®NA ❑Yes ❑No 21 NA ❑Yes ❑No D NA ❑Yes ❑No ❑NA <br /> o erational?" <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> starting test <br /> Test Start Time: 1:43PM 1:43PM <br /> Initial Reading (Rt): 1.2071 Inches 1.08W Indies Inches Inches <br /> Test End Time: 1:58PM 1:58PM <br /> Final Reading(Rr}; 1.2052 Inches 1.0825 Inches Inches Inches <br /> Test Duration: 15 Minutes 15 Minutes <br /> Chan a in Readin R -R: 0.0019 0.0013 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Teat Result: 0 Pass ❑Vail 0 Pass ❑Fall ❑ Pass ❑Fail ❑ Pass O Fail <br /> Was sensor removed for testing? 0 Yes p No ❑NA ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes p No ❑NA, <br /> $ Was sensor properly replaced and G3 Yes ❑No ❑NA ®Yes p No ❑NA ❑Yes ❑No ❑NA ❑Yes O No ❑NA <br /> # verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for Tailed rests) <br /> "Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment <br /> testing scope of work". <br /> Adjusted and tightened clamp in Disp. #//8. Retested. <br /> Replaced test boot in Disp. #11/12. Retested. <br />