Laserfiche WebLink
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />❑ Pressure <br />❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester <br />Equipment Resolution: +/-0.002" <br />Vapor Spill Box # 87 <br />Vapor Spill Box # 91 <br />Bucket Diameter: <br />12" <br />12" <br />Bucket Depth: <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and I <br />10 min. <br />10 min, <br />starting test: <br />Test Start Time: <br />8:06 am <br />7:08 am <br />Initial Reading ( R a)� <br />4.5082 <br />5.4206 <br />Test End Time: <br />8:21 am <br />7:23 am <br />Final Reading (RF); <br />4.5081 <br />5.4214 <br />Test Duration: <br />15 min. <br />15 min. <br />Change in Reading (Rp-R,): <br />0.0001 <br />0.0008 <br />Pass/Fail Threshold or <br />+/-0.002" <br />LO <br />+/-0.002" <br />Criteria: <br />Test Result: <br />Pass ❑ Fail <br />® Pass ❑ Fail <br />Comments —(include information on repairs made prior to testing, and recommended fo11 - f etsts <br />FH <br />ENVIRONMENTAL <br />DEPARTMENT- <br />