Laserfiche WebLink
E <br />11 <br />Facility is Not Equipped With Spilll'Overfill Containment Boxes E] <br />Spi I [/Overfill Containment Boxes are Present, but were Not Tested El <br />Test Method Developed By: [] Spill Bucket Manufacturer Industry Standard ❑ Professional Engineer <br />El Other (Specify) <br />Test Method Used: E] Pressure C] Vacuum Z Hydrostatic <br />El Other (Specify) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br />Fill Spill Box # 87 <br />Fill Spill Box 0 91 <br />Bucket Diameter: <br />12" <br />12" <br />Bucket Depth: <br />101? <br />to,, <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min, <br />Test Start Time: <br />8:06 am <br />7:08 am <br />Initial Reading (Rj):_ <br />3,5907 <br />6.1790 <br />Fest End Time: <br />8:21 am <br />7:23 am <br />Final Reading (RF): <br />3.5907 <br />6.1797 <br />Test Duration: <br />15 min. <br />15 min. <br />Change in Reading (RF -RI): <br />0.0000 <br />0.0007 <br />Pass/Fail Threshold or <br />Criteria: <br />+/-0.00211 <br />+/-0.00211 <br />Test Result: <br />0 Pass 0 Fail <br />[Z Pass 0 Fail <br />Comments — (include information on repairs made prior to testing and recommended follo,,v-iipfor failed tests) <br />E:C%5 b, 3 Z0 1 <br />AENTAL HEALTH <br />DEPARTNIENT <br />