File MH19589 Page T1-2 of 2 Issued: 1-30-97 <br /> LOW TEMPERATURE BENDING TEST: <br /> METHOD <br /> Representative samples of the CP1502 were conditioned in a <br /> freezer maintained at a temperature of 0°C for at least 24 h. <br /> Immediately upon removal from the freezer, the samples were then <br /> wrapped around a mandrel having a diameter of ten times the <br /> internal pipe diameter. The samples were then allowed to return <br /> to room temperature and the interstital space was subjected to a <br /> aerostatic pressure of 10 psig for a period of 5 min. <br /> RESULTS <br /> There was no evidence of leakage or damage to the pipe. <br /> BENDING TEST: <br /> METHOD <br /> Representative samples of the CP1502 were successively bent <br /> to an arc having a radium of 60, 50, 40 and 30 percent of the <br /> manufacturer' s minimum recommending bending radius (24 in. ) . <br /> Each bending shall be repeated 50 times . Following the bending <br /> cycles, the interstitial space of each sample was subjected to <br /> aerostatic pressure of twice the rated pressure for a period of <br /> S min. and examined for evidence of leakage . <br /> RESULTS <br /> There was no evidence of leakage or damage to the pipe . <br /> LMD/TAS :nsc <br /> NKDLS <br />