SWRCB, January 2002 <br />Page _7 of —9- <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: VISUAL — <br />TAPE MEASURE <br />Equipment Resolution: + / 0.002" <br />Fill Sump # 87(1) <br />MRSEENEEM <br />Fill Sump # 87(2) <br />SEEN= <br />Fill Sump # 87(3) <br />Fill Sump # 91 <br />Sump Diameter: <br />48" <br />48" <br />48" <br />48" <br />Sump Depth: <br />68" <br />67" <br />67" <br />68" <br />Height from "Tank Top to Top of <br />Highest Piping Penetration: <br />N/A <br />N/A <br />N/A <br />N/A <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />29„ <br />32" <br />28" <br />31" <br />Condition of sump prior to <br />testing: _ <br />DRY <br />DRY <br />DRY <br />DRY <br />Portion of Sump Tested <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />Sump Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: _ <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time <br />10:36 <br />10:36 <br />10:36 <br />11:48 <br />Initial Reading (Rj): <br />5.6645" <br />7.0603" <br />6.6707' <br />6.8480" <br />Test End Time: <br />10:52 <br />10:52 <br />10:52 <br />12:03 <br />Final Reading (RF): <br />5.6644" <br />7.0602" <br />6.6706" <br />6.8480" <br />Test Duration: <br />15 MIN <br />15 MIN <br />15 MIN <br />15 MIN <br />Change in Reading (RF -R,): <br />-0.00011, <br />-0.00011, <br />-0.00011, <br />0.0000" <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/_ 0.002" <br />+/_ 0.002" <br />+/_ 0.002" <br />Test Result: <br />El Pass ❑ Fail <br />® Pass ❑'Fail <br />® Pass El Fail <br />® Pass ❑ Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Elves ❑ No ®NA <br />Elves ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Was sensor removed for testing? <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />M Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />Comments= (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />