SWRCB, January 2002 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Page _8— of 9 <br />g — — <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer <br />❑ Other (Spec) <br />® Industry Standard <br />❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Spec) <br />❑ Vacuum <br />® Hydrostatic <br />Test Equipment Used: VISUAL <br />Equipment Resolution: 1/16" <br />=ME <br />Spill Box # 87(1) FILL <br />Spill Box # 87(1) <br />VAPOR <br />Spill Box # 87(2) FILL <br />Spill Box # 87(2) <br />VAPOR <br />Bucket Diameter: <br />12" <br />12" <br />12" <br />12" <br />Bucket Depth: <br />15" <br />15" <br />14.50" <br />16" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: _ <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time: <br />11:00 <br />11:00 <br />11:00 <br />11:00 <br />Initial Reading (Rj): <br />13.50" <br />13.50" <br />13" <br />14.50" <br />Test End Time: <br />12:00 <br />12:00 <br />12:00 <br />12:00 <br />Final Reading (Rf.-): <br />13.50" <br />13.50" <br />13" <br />14.50" <br />Test Duration: <br />1 HR <br />1 HR <br />1 HR <br />1 HR <br />Change in Reading (RF-Rj): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: _ <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />Test Result: <br />1 ® Pass ❑ Fail <br />® Pass <br />❑ Fail <br />0 Pass <br />❑ <br />Fail <br />` ® Pass <br />El Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />APR 2 0 2015 <br />VI I <br />