Laserfiche WebLink
Station # Arco SS 2093 Date 9/19 2014 <br />UESIM <br />WIT174-11M <br />This letter certifies that the annual leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br />flow threshold trip rate of 3 gph at 10 PSI. <br />�,ettler-Rvan Ingi <br />Techniciai <br />1:1= <br />2 <br />3 <br />4 <br />5 <br />Product <br />87 <br />91 <br />Manufacturer <br />VR <br />VR <br />Model <br />848480 <br />848480 <br />Full Operating Pressure (psi) <br />32 Si <br />32 S! <br />Line Bleed Back (ml) <br />NA <br />NA <br />Trip Time (sec) <br />NA <br />NA <br />Metering Pressure (psi) <br />NA <br />NA <br />RE Holding Pressure (psi) <br />20psi <br />20psi <br />Test Leak Rate (ml/min)(gph) <br />1 <br />1 <br />PASS or FAIL <br />P <br />P <br />WIT174-11M <br />This letter certifies that the annual leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br />flow threshold trip rate of 3 gph at 10 PSI. <br />�,ettler-Rvan Ingi <br />Techniciai <br />1:1= <br />