Laserfiche WebLink
SWRC$, January 2002 <br />R_ FII.I. RISER CONTAINMENT SUMP TESTING <br />Page _7_ of _9_ <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: INCON SUMP <br />TESTER <br />Equipment Resolution: + / - 0.002" <br />Fill Sump # 87(1) <br />Fill Sump # 87(2) <br />Fill Sump # 87(3) <br />Fill Sump # 91 <br />Sump Diameter: <br />48" <br />48" <br />48" <br />48" <br />Depth: <br />68" <br />67" <br />67" <br />68" <br />,-Sump <br />Height from Tank Top to Top of <br />Hi hest Piping Penetration: <br />N/A <br />N/A <br />NIA <br />N/A <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />29" <br />32" <br />28" <br />31" <br />Condition of sump prior to <br />testing: <br />DRY <br />DRY <br />DRY <br />DRY <br />Portion of Sump Tested <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />Sump Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time: <br />10:45 AM <br />10:23 AM <br />10:23 AM <br />10:23 AM <br />Initial Reading (Rj): <br />4.1529" <br />3.8423" <br />4.6072" <br />6.4635" <br />Test End Time: <br />11:00 AM <br />10:39 AM <br />10:39 AM <br />10:39 AM <br />Final Reading (RF): <br />4.1529" <br />3.8420" <br />4.6071" <br />6.4636" <br />Test Duration: <br />15 MIN <br />15 MIN <br />15 MIN <br />15 MIN <br />Change in Reading (RF-Rj): <br />0.0000" <br />-0.0003" <br />-0.0001" <br />0.0001" <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/-0.002" <br />+/-0.002" <br />+/- 0.002" <br />Test Result: <br />OPass ;, ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />0, Pass ❑'Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes []No ®NA <br />❑ Yes ❑ No ®NA <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA <br />® Yes [:]No ❑NA <br />®Yes ❑ No [-INA <br />® Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes ❑ No [:1 NA <br />®Yes ❑ No [:1 NA <br />®Yes El No [--]NA <br />®Yes F1 No [-]NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS <br />