Laserfiche WebLink
Test Equipment Used: Vaporless VMI LDT-890 <br />Tank number <br />LINE LEASDETECTOR (LLD) <br />TE1' REPORT <br />TEST DATE: <br />June 7, 2011 <br />Gasoline - 87 <br />Al. FACILITY <br />A2. OWNER <br />Name <br />Quik Stop Market #124 <br />Name <br />Quik Stop Markets, Inc. <br />Address <br />505 N. Main Street, Manteca, CA 95336 <br />Address <br />4567 Enterprise Street, Fremont, CA 94538 <br />Phone # <br />510-657-8500 <br />Phone # <br />510-657-8500 <br />Contact <br />Michael Karvelot <br />Contact <br />Michael Karvelot <br />Resiliency (ml) <br />100 <br />A3. C U P A <br />A4. TESTING <br />CONTRACTOR <br />Name <br />San Joaquin County Environmental Health <br />Name <br />Walton Engineering, Inc. <br />Address <br />600 E. Main Street, Stockton, CA 95202 <br />Address <br />P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified <br />June 1, 2011 <br />Lic # <br />617238 A, B, Haz <br />Inspector <br />None <br />Contact <br />Dulcinea Covan <br />Phone # <br />209-468-8257 <br />Phone # <br />916-373-1166 <br />30 <br />I. MECHANICAL LINE LEAK DETECTOR TEST RESULTS <br />5 <br />Test Equipment Used: Vaporless VMI LDT-890 <br />Tank number <br />1 <br />Product contained <br />Gasoline - 87 <br />Leak Detector Type <br />MLLD <br />Leak detector make/model <br />Red Jacket FX <br />Serial number <br />116-056 <br />Functional Element Holding (psi) <br />24 <br />Resiliency (ml) <br />100 <br />Test leak rate (gph) <br />3.00 <br />Pump pressure (psi) <br />24 <br />Metering pressure (psi) <br />12 <br />Pressure Restriction Reduction (psi) <br />12 <br />Length of Restriction Test (seconds) <br />30 <br />Full Flow Opening time (seconds) <br />5 <br />TEST RESULT <br />PASS <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />2 <br />Gasoline - 89 <br />MLLD <br />VMI 99LD-2000 <br />4051056 <br />30 <br />80 <br />3.00 <br />30 <br />11 <br />19 <br />30 <br />3 <br />PASS <br />3 <br />Gasoline - 91 <br />MLLD <br />FE Petro STP -MLD <br />1121043 <br />40 <br />60 <br />3.00 <br />40 <br />25 <br />15 <br />30 <br />2 <br />PASS <br />WALTON <br />Signature: <br />4dG6NEEMNG, MC. <br />Technician: Date: June %, 2011 <br />