Laserfiche WebLink
CERTIFICATE O NDERGROUND STORAGE TANK SYSTEM TESTING <br /> NDE ENVIRONMENTAL CORPORATION JrDE <br /> 8906 WALL STREET, SUITE 306 <br /> AUSTIN, TEXAS 78754 <br /> (512) 719-4633 <br /> FAX (512) 719-4986 <br /> TEST RESULT SITE SUMMARY REPORT <br /> TEST TYPE: Alert 4000 <br /> TEST DATE: December 1, 1994 WORK ORDER NUMBER: 963222 <br /> CLIENT: TOSCO NORTHWEST COMPANY SITE: BP 1-1195 <br /> 601 UNION ST 16500 I-5 <br /> SUITE 2500 LATHROP, CA 95338 <br /> SEATTLE, WA 98101 <br /> ATTN: LYNN CHUN <br /> The following tests were conducted at the site above in accordance with all applicable portions of Federal, NFP A and local regulations. <br /> Tank Tests <br /> I" TANK U #UME U <br /> TAf+fK Pt if31 St3 f APACtTY 13[A 1fETER TANK Om E #*kES1JLT <br /> I�ft�tff3EF3 itrhas} ftEtJLT ) <br /> 1 PLUS 8,000 92.00 PASS —0.006 PASS <br /> 2 SUPER 6,000 92.00 PASS —0.002 PASS <br /> 3 REG UNLEAD 10,000 92.00 PASS —0.029 PASS <br /> 4 WASTE OIL 500 46.00 PASS 0.025 PASS <br /> Line and Leak Detector Tests <br /> FSE 1t1t,T <br /> 1/C3Lt3f E LEAK LEAK <br /> TANK I�Rf DUCT { , (€' a fei[ DETECTOR .:.DETECTOR <br /> NttI+ E lonclusive} PRESENT RESULT <br /> A B C D <br /> 1 PLUS 0.005 P YES PASS <br /> 2 SUPER 0.005 P YES PASS <br /> 3 REG UNLEAD 0.011 P YES PASS <br /> 4 WASTE OIL <br /> NDE appreciates the opportunity to serve you,and looks forward to working with you in the future.Please call any time,day or night,when you need us. <br /> NDE Customer Service Representative: Test conducted by: <br /> JERRY BELLOLI DAVID NATHIE <br /> Reviewed: el4 ber: <br />