Laserfiche WebLink
r <br /> Triangle viro ental Inc <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 30225 <br /> Tank #. / Test Date: 10/18/2001 <br /> Product: Unleaded Premium Work#: 7405577 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 11849 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> I ' <br /> Product Level(in): L/D Serial#: 9474 <br /> Liquid Volume(Gals): i Line Drain Back(ml): 110 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 32 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> 1 <br /> ! Test Method: TEI LT-3 <br /> Test End Time: <br /> Test Rate(g2it- <br /> Pump Brand: FE Petro <br /> Test Re N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 11:54:00 AM <br /> Test Method: ULLAGE Line End Time: 12:09:00 PM <br /> UllageVolume(gals.): Line Start Level: 255 <br /> I Line End Level: 245 <br /> Ullage Test Time: <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.011 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />