Laserfiche WebLink
r t <br /> TriangleEnvironmental Inc <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 30225 <br /> Tank #: 1 Test Date: 10/18/2001 <br /> Product: Unleaded Regular Work#: 7405577 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 11849 Manufacturer: FE Petro <br /> Diameter(in): L/D Model: FE <br /> Product Level(in): L/D Serial#: 01080902 <br /> Liquid Volume(Gals): Line Drain Back(ml): 140 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 32 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(g21t <br /> ' Pump Brand: FE Petro <br /> Test Re : N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 11:54:00 AM <br /> Test Method: ULLAGE Line End Time: 12:09:00 PM <br /> UllageVolume(gals.): Line Start Level: 270 <br /> Ullage Test Time: Line End Level: 230 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.042 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 3 <br />