Laserfiche WebLink
UNDER DISPAINSER CONTAINMENTODC) TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />Descriotion Diso # 8 Sat <br />UDC manufacturer <br />Total Containment <br />UDC material <br />Poly <br />UDC depth (inches) <br />38" <br />Height from UDC bottom to highest <br />piping penetration <br />8" <br />Height from UDC bottom to lowest <br />electrical penetration <br />12" <br />Condition of UDC prior to testing <br />Dry <br />Portion of UDC tested <br />Entire <br />Type of shut -down present <br />Sensor <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced after testing? <br />Yes <br />Depth of water level from UDC bottom (in.) <br />14 <br />Wait time for water level to stabilize (hr:min) <br />0:05 <br />Test start time <br />2:17 PM <br />Initial Probe Reading <br />2.6691 <br />Test end time <br />2:32 PM <br />Final Probe Reading <br />2.6703 <br />Test duration (hr:min) <br />0:15 <br />Change in water level (± 0.0000 inches) <br />0.0012 <br />Pass/Fail threshold (±0.0020 inches / } Hr.) <br />0.0020 <br />TEST RESULT <br />PASS <br />Comments: <br />© 2006 Walton Engineering, Inc. <br />