Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00076 <br /> Tank #e 1 Test Date: 3l 8/98 <br /> Product: Unleaded Regular Work#: 30633 <br /> !w1mling z! <br /> Em <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 10000 Manufacturer: Red Jacket <br /> Diameter(in): 94 L/D Model: FX-1 <br /> Product Level(in): 32 L/D Serial#: 092194-7356 <br /> Liquid Volume(Gals): 2926 Line Drain Back(ml): 125 <br /> Liquid Percent(%): 29.3% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 10 <br /> Coef.of Expansion: 0.000665 Metering Pressure(psi): 9 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): 0.9 <br /> Test Start Time: 10:00:00 PM Test Method: TEI LT-3 <br /> Test End Time: 10:20:00 PM Pump Brand: Tokheim <br /> Test Rate(gph): 0.02 System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 12:10:00 AM <br /> Test Method: ULLAGE Line End Time: 12:25:00 AM <br /> UllageVolume(gals.): 7074 Line Start Level: 300 <br /> Ullage Test Time: 10:00:00 PM <br /> Line End Level: 290 <br /> Ullage Vacuum(psi): 1.9 Line Test Rate(gph): -0.01 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 2 <br />