Laserfiche WebLink
•e R <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00076 <br /> Tank#: 2 Test Date: ✓/ 8/98 <br /> Product: Unleaded Premium Work#: 30633 <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 10000 Manufacturer: Red Jacket <br /> Diameter(in): 94 L/D Model: XLD <br /> Product Level(in): 27 L/D Serial#: UNK <br /> Liquid Volume(Gals): 2313 Line Drain Back(ml): 175 <br /> Liquid Percent(%): 23.1% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 8 <br /> Coef.of Expansion: 0.000664 Metering Pressure(psi): 8 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): 0.7 <br /> Test Start Time: 10:30:00 PM Test Method: TEI LT-3 <br /> Test End Time: 10:50:00 PM Pump Brand: Tokheim <br /> Test Rate(gph): 0.02 System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 12:10:00 AM <br /> Test Method: ULLAGE Line End Time: 12:25:00 AM <br /> UllageVolume(gals.): 7687 Line Start Level: 355 <br /> Ullage Test Time: 10:30:00 PM Line End Level: 350 <br /> Ullage Vacuum(psi): 1.7 Line Test Rate(gph): -0.00528402 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 3 <br />