Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. e <br />3131 Fairhaven Drive <br />Bakersfield, CA 93308 RECE <br />(805) 322-9827 JUL 0 6 <br />r'NVIRONMEN'll <br />PERMIT/SES 'rig:` <br />ANNUAL 3-STEP RED JACKET LEAK DETECTOR TEST <br />• QUIK STOP MARKET <br />LOCATION Stockton, CA. *76 DATE 06/13/90 - <br />PRODUCT: Regular, Unleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use separate form for each Tank. <br />(1) Running Pressure 24 2 (2) Shut-off Pressure 35 <br />(3) Amount of Product Released thru Bibcock to Zero 2 —OZ. <br />(4) With Valve Open --Start STP - List Pressure 3 P.S.I., <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 7 P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created List <br />time for Gauge to Reach Zero min. 10 see., <br />(7) Turn the STP back on Keep Leak Rate at Bibcock - List pressure <br />5 P.S.I. Flow Rate at Nozzle 1.0 G.P.M., <br />(8) Stop Leak with STP still on - Does Leak Detector reset _X yes no <br />If yes - How long to reset —min 10 sec., <br />(9) Turn STP off - List pressure 25 P.S.I., <br />(10) Turn STP back on - List time to reach pressure rise min. 10 sec. <br />(11) List Pressure 30 P.S.I., <br />(12) Open Nozzle and List Pressure 24 —P.S.I. <br />SATISFACTORY LEAK DETECTOR x Yes No. <br />kat" <br />Model <br />•- Jacket I Date Code <br />