Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. <br />3131 Fairhaven Drive <br />Bakersfield, CA 93308 <br />(805) 322-9827 <br />ANNUAL 3 -STEP RED JACKET LEAK DETECTOR TEST <br />OWNER QUIK STOP MARKET <br />LOCATION Stockton, CA. *76 DATE 06Z13Z90 <br />PRODUCT: Regular Unleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use separate form for each Tank. <br />(1) Running Pressure 22 1 (2) Shut -Off Pressure 30 1 <br />(3) Amount of Product Released thru Bibcock to Zero 2 —OZ. <br />(4) With Valve Open --Start STP - List Pressure 7 P.S.I., <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 8 P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br />time for Gauge to Reach Zero min. 2 sec., <br />(7) Turn the STP back on Keep Leak Rate at Bibcock - List pressure <br />8 P.S.I. Flow Rate at Nozzle 1.0 G.P.M.1 <br />(8) Stop Leak with STP still on - Does Leak Detector reset _X yes no <br />If yes - How long to reset min 10 sec., <br />(9) Turn STP off - List pressure 20 P.S.I., <br />(10) Turn STP back on - List time to reach pressure rise min. 10 sec. <br />(11) List Pressure 30 -P.S.I., <br />(12) Open Nozzle and List Pressure 22 P.S.I. <br />SATISFACTORY LEAK DETECTOR x Yes No. <br />Model Red Jacket , Date Code & Serial * 10587-1196 <br />