Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. <br />3131 Fairhaven Drive <br />Bakersfield, CA 93308 <br />(805) 322-9827 <br />pUG <br />ANNUAL 3 -STEP RED JACKET LEAK DETECTOR TEST ESNti1" <br />�v� W� �G <br />OWNER QUIK STOP MARKET <br />LOCATION Stockton #76 DATE July 27, 1989 <br />PRODUCT: Regular, pleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use separate form for each Tank._ <br />(1) Running Pressure ­22 -9 (2) Shut -Off Pressure 22 <br />(3) Amount of Product Released thru Bibcock to Zero 3 oz. <br />(4) With Valve Open ---Start STP - List Pressure 2- —P.S.I., <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 2 P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br />time for Gauge to Reach Zero <br />min. 5 sec., <br />(7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br />2 -P.S.I. - Flow Rate at Nozzle 1.5 G.P.M., <br />(8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br />If yes - How long to reset min 10 sec., <br />(9) Turn STP off - List pressure 20 -P.S.I.,. <br />(10) Turn STP back on - List time to reach pressure rise min. 2 sec. <br />(-11) List Pressure 22 <br />(12) Open Nozzle and List Pressure 22 P.S.I. <br />SATISFACTORY LEAK DETECTOR x Yes No. <br />LEAK DETECTOR <br />Model Red Jacket Date Code & Serial <br />