Laserfiche WebLink
0 0 <br />x V <br />WESTERN AMERICA TANK TESTING, INC. <br />3131 Fairhaven Drive <br />Bakersfield, CA 93.308 <br />(805) 322-9827 <br />ANNUAL 3 -STEP RED JACKET LEAK DETECTOR TEST <br />OWNER QUIK STOP MARKET <br />LOCATION Stockton #76 DATE _ July 27, 1989 <br />PRODUCT: Regular, Unleaded, Premium Unleaded, Diesel (Circle one) <br />NOTE: Use separate form for each Tank <br />(1) Running Pressure 20 (2) Shut --Off Pressure 22 <br />(3) Amount of Product Released thru Bibcock to Zero 2 OZ. <br />(4) With Valve Open ---Start STP -- List Pressure 2 <br />(5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br />Rate 2 <br />P.S.I., <br />(6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br />time for Gauge to Reach Zero min. 3 sec., <br />(7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br />2 F.S.I. - Flow Rate at Nozzle 1.2 G.P.M., <br />(8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br />® If yes - How long to reset min 15 sec., <br />(9) Turn STP off - List pressure 22 P.S.I., <br />(10) Turn STP back on - List time to reach pressure rise min. 3 sec. <br />(11) List Pressure 22 P.S.I., <br />(12) Open Nozzle and List Pressure 20 P.S.I. <br />SATISFACTORY LEAK DETECTOR X ._- Yes No. <br />LEAK DETECTOR <br />Model Red Jacket Date Code & Serial # <br />