Laserfiche WebLink
11 <br />• <br />The USIP's gas/liquid detector consists of two basic parts: gas/liquid sensors and <br />system controller. Standard Model GW -6204 is a wall mounted type gas/liquid <br />detector, which uses 115± 10VAC/60Hz as the main power source. The standard <br />model GW -6204 includes one audio horn, four RED LED alarms for hydrocarbon <br />vapors leaks, four RED LED alarm for water leaks, four YELLOW LED Fail lights, <br />four GREEN LED POWER lights, four METER readouts and one TEST switch for <br />all functions. (See Figure 3.) <br />A. CONTROLLER <br />AC Power Input: <br />115 ± 10VAC/60Hz, UL -Listed <br />Alarm Circuit: <br />Fail, Alarms <br />Audio Alarm Outputs: <br />95 dB at 100 cm, (pulsed tone, sound one minute and <br />30 minutes each cycle), UL -Listed <br />LED Indicators: <br />Power (Green), Fail (Yellow), Alarms (Red) <br />Readout Range: <br />0-1000 ppm, or 0-100% LEL <br />Panel Controls: <br />Zero Setpoint Adjust, Span Setpoint Adjust, circuit <br />test switch <br />Relay Control: <br />NO, NC, COM: SPDT 7A-125VAC, UL -Listed <br />Power Consumption: <br />14 watts <br />Protection Fuse: <br />0.5A <br />Dimensions: <br />8"W x 10"H x 6"D <br />Weight: <br />3.0 lbs. <br />Panel Box: <br />NEMA type 4 enclosure, UL -Listed for indoor & outdoor, <br />oil & water tighted. <br />3 <br />