Stockton Army Air Facility, Tank removal application page 2 <br />2000 Stimson Rd., Stockton. <br />Previous UGT removals (tanks 1, 2, and 3) noted significant soil contamination in <br />soil boring "B-3" from 15 feet to 30 feet below grade just northwest of tanks #4 <br />and #5. The three onsite monitoring wells to the west of tanks #4 and #5 have <br />recorded the groundwater gradient to the northeast and as such, are not in a <br />position to represent groundwater conditions down -gradient from the tanks <br />proposed to be removed. If soil contamination is detected during this <br />removal, an additional soil and groundwater investigation will be required. <br />The soil and groundwater lateral and vertical extents (up -gradient, down - <br />gradient, laterally to the east and vertically to the Fall -1978 depth to first <br />groundwater) will need to be delineated. <br />Additionally, if soil contamination is discovered during tank #4 and #5's <br />removal, pea gravel will not be allowed to be used to backfill the tank pit. <br />Please submit a revision to Michael Infurna for your application that addresses <br />the above noted items. You may contact Mr. Infurna at (209) 468-3454 if you <br />have any questions. <br />Thank you for your cooperation, <br />Michael J. Infur a Jr., Senior REHS <br />UGT Investigation / Site Mitigation Unit IV <br />MI/ <br />c: A. K. Jain - DSA, 13001 St., Ste 700, Sac., 95814 <br />c: Vern Elarth - Versar, 7844 Madison Ave, Ste 167, Sac., 95628 <br />c: Stockton AASF - Sgt. Curt Lance, 2000 Stimson Rd, Stockton, 95206 <br />c: Captain B. Anderson, National Guard/C.A.S.E., 980 Goethe, Sac., 95826 <br />