Laserfiche WebLink
SWRCB_January 2002 Page 4 Of 7 <br /> WATERLOO FOOD&FUEL <br /> 3032 E. Waterloo Road <br /> Stockton,CA 95205 <br /> May 31,2005 <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: Sump Manufacturer [X] Industry Standard ]Professional <br /> Engineer <br /> [ ]Other(Specof) <br /> Test Method Used: ( ] Pressure [ ]Vacuum [X j Hydrostatic <br /> [ ]Other(S eci <br /> Test Equipment Used: CAJLDW EJLL LEVEL GAUGE Equipment Resolution: 0.0025 <br /> Super Unlead ReLrular Unleaded "Diesel <br /> S=p Diameter: 38 INCH 38 INCH 38 1NC:I--I <br /> Sump Depth; 36 INCH 36 INCH 36 INCH <br /> Sump Material: _ _ <br /> Fiberglass Fiber lass Fiber lass <br /> Height from Tank Top to Top of 18 INCH 18 INCH 17 INCH <br /> Hi hest Pi2ing Penetration: <br /> IIeight from Tank Top to Lowest 20 NCI F 4 21 TWIT 21 INCH <br /> Electrical Penetration: <br /> Condition of sump prior to testin : _21- <br /> D llty <br /> Portion of SumR Tostcd I 24 INCH 21 INCH 21 INCH <br /> Does turbine shut down when sump [X]YES [ l NO [X]YES [ I NO [x]YES[ ]NO ( ]YRS( J NQ <br /> sensor detects liquid(both product& ( JNA () NA ( JNA [ JNA <br /> water <br /> Turbine shutdawu res onsc Bute; <br /> Is systern progmrnmed for fait-safe [X]YES ( ]NO [X] YES[ ]NO [X]YES[ ]NO [ I YES[ ]NO <br /> Shutdown? [ )NA [I NA I .I NA ( JNA <br /> Was fail-safe verified to be [XJ YES[ j NO (x)YES[ ]NO [X]YES[ ]NO [ ]YES[ ]NO <br /> n erational? L l NA []NA ( ]NA I JNA <br /> Wait time between applying <br /> pressure/vacuum/wa.tcr and starting ,5 MINUTES 5 M.M7ES 5 MINUTES <br /> test: <br /> Test Start Time: 1:30 P.M, 11:10 A.M. '10;15 A.M. <br /> Initial Readina(Rl): 24 INCH 23 INCH 23 INC-11 <br /> Test End Time-- 10:00 A.M. 11:40 A.M. 10:45 A,M. <br /> Final Readin RO: 24 INCH 23 INCH 23 INCH <br /> Tcst Duration: 30 MINOTES 30 MINUTES30 MINUTES <br /> Change,in Read in Rf-Rll -0. -0- _..�......._..,._... -.,.,.W "-0 — <br /> Pass/Fail Threshold or Criteria: -0- .0. '0- <br /> 'iLesiResult:.. . Ixl r°Ass ( ].r.•Alt... .. .1dC].:iASS C.I't;AI( dxl .I'a.5S. I•..1.FA1L..,,,. ,,;,', ,;;[]P? ,+.I.�NO <br /> Was sensor removed for testing? [xl YES_�..I]NO [X]YES [ ]NO [X]YES ( )NO [ ]YPS [ J NO <br /> I NA C INA f INA NA <br /> Was sensor irciperty replaced and [Xl YES I I NU (X1 YLS C ]NO [X] YES [ ]NO [ ]YE.S[ J NO <br /> vcritae(I functional after testin '? [ ]NIA ( ]N/A j ]N!A [ ]NA <br /> M __... <br /> Comments—(include information on repairs made prior to testing,and recontnaended follow-up for tailed tests) <br /> I If the entire depth of the surtrp is not tested,specify how much was tested. if the answer to gja of Clic questions indicated with an asterisk(*)is "NO"or <br /> "NA",the entire sump must be tested, ('SWRCB LG-160) <br />