Laserfiche WebLink
SWRCB,January 2002 Page_5_of—5- <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps <br /> Fill Riser Containment Sumps are Present,but were Not Tested <br /> Test Method Developed By: Sump Manufacturer ®Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure Vacuum ®Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: INCON TS-STS UNIT Equipment Resolution: N/A <br /> Fill Sump#FILL Fill Sump# Fill Sump# Fill Sump# <br /> MIDDLE <br /> Sum Diameter: 38" 38" <br /> Sum De th: 40.5" 41" <br /> Height from Tank Top to Top of 10" N/A <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 8" 14" <br /> Electrical Penetration: <br /> Condition of sump prior to GOOD GOOD <br /> testing: <br /> Portion of Sump Tested 2"ABOVE SUMPS 2"ABOVE SUMPS <br /> HIGHEST PIPING HIGHEST PIPING <br /> PENETRATION PENETRATION <br /> Sump Material: FIBERGLASS FIBERGLASS <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MINUTES 15 MINUTES <br /> starting test: <br /> Test Start Time: 10:45 11:03 10:45 11:01 <br /> Initial Reading(Ri): 5.2316 5.2303 4.9051 4.9044 <br /> Test End Time: 11:00 11:16 11:00 11:16 <br /> Final Reading(RF): 5.2305 5.2294 4.9045 4.9042 <br /> Test Duration: 1 HOUR 1 HOUR 1 HOUR I HOUR <br /> Change in Reading(RF-R,): -0011 -.0009 -.0006 -.0002 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002 .002 <br /> Test Result: 0 Pass'' Fail ® Pass Fail Pass Fail Pass Fail <br /> Is there a sensor in the sump? ®Yes No ®Yes No Yes No Yes No <br /> Does the sensor alarm when <br /> either product or water is ®Yes No NA ®Yes No NA Yes No NA Yes No NA <br /> detected? <br /> Was sensor removed for testing? ®Yes No NA ®Yes No NA Yes No NA Yes No NA <br /> Was sensor properly replaced and ®Yes No NA ®Yes No NA Yes No NA Yes No NA <br /> verified functional after testing?- <br /> — L <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> *The"Middle" sump was hydrostatically tested 2" above sump collar. No product piping was located <br /> in sump. <br /> *Fill sump and the "Middle" sump pass the industry standard hydrostatic test. No repairs are needed at <br /> present time. <br />