Laserfiche WebLink
i <br /> f <br /> SWRCB,January 2002 <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer Q Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum f-x�Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> Fill Sump UE040001 <br /> Sum Diameter: 38" <br /> Sump Depth: 40" <br /> Height from Tank Top to Top of 10" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 8„ <br /> Electrical Penetration: <br /> Condition of sump prior to Good <br /> testing: <br /> Portion of Sump Tested 2"above piping <br /> Sump Material: Fiberglass <br /> Wait time between applying <br /> pressure/vacuum/water and 15 min. <br /> starting test: <br /> Test Start Time: 9:25am 9:40am <br /> Initial Reading(RI): 3.9564 3.9560 <br /> Test End Time: 9:40am 9:55am <br /> Final Reading(RF): 3.9560 3.9559 <br /> Test Duration: 15 min. 15 min. <br /> Change in Reading(RF-Rj): .0004 .0001 <br /> Pass/Fail Threshold or Criteria: .002 .002 <br /> Test Result: ❑X Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Is there a sensor in the sump? ❑X Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is ❑1'es [E]No ❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> detected? <br /> Was sensor removed for testing? ❑X Yes ❑No ❑NA ❑Yes❑No❑NA F-1 Yes❑No❑NA El Yes El No El NA <br /> Was sensor properly replaced and ❑Yes IK No ❑NA <br /> verified functional after testing? ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Sensor was removed for testing, but not tested and was reinstalled to the lowest point. <br />