Laserfiche WebLink
SEP 0 9 <br /> Addendum <br /> Date of Test: August 17,2016 <br /> Certified Tester: Pat Banbury <br /> Report Prepared by: Jeff Stevenson <br /> Report ID: Stockton AT&T CA TA61.81 Diagnostic Report to 17-Aug-16.doc <br /> Glossary of Acronyms used <br /> ATG Automatic Tank Gauge <br /> UPSS Underground Petroleum Storage System <br /> USEPA United States Environmental Protection Agency <br /> CARB California Air Resources Board <br /> The underground pipe and tank configurations contained in this report are deduced from information gathered at the <br /> site by Leighton O'Brien and by information given to Leighton O'Brien by the client. <br /> Details of Line Test <br /> UE042U00I Transfer P mp To UE042A005 Belly Tank <br /> Line PASS Time psi qaVhr <br /> Valve NA 13:03:09 51.37 0.120 <br /> Tested Wet <br /> Start 12:45:00 <br /> Date 17-Aug-16 <br /> Unit SN <br /> Cert No. 50264 <br /> Stockton AT&T CA TA6181 Diagnostic Report to 17-Aug-16.doc Page 3 of 3 <br />