RECEIVED <br /> SWRCB,January 2002 AUG 2 3 2016 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: ❑Piping Manufacturer El Industry Standard ❑Profe k 9J_ T <br /> ❑Other(Spec) <br /> Test Method Used: 0 Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: 4"dial gauge Equipment Resolution: .2 <br /> Supply 1 UE0420001 Supply 2 UE0420001 Vent UE0420001 Emergency Return <br /> Piping Material: Poly Poly Fiberglass Fiberglass <br /> Piping Manufacturer: Western Fiberglass Western Fiberglass AO Smith AO Smith <br /> Piping Diameter: 2" 2" 4" 3" <br /> Length of Piping Run: 15' 15' 20' 25' <br /> Product Stored: Diesel Diesel Diesel Diesel <br /> Method and location of test boot test boot test boot test boot <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 15 min 15 min 15 min Visual failure <br /> starting test: <br /> Test Start Time: 9:30am 9:30am 9:30am <br /> Initial Reading(Rj): 5 psi 5 psi 5 psi <br /> Test End Time: 10:30am 10:30am 10:30am <br /> Final Reading(RF): 5 psi 5 psi 5 psi <br /> Test Duration: 1 hour 1 hour 1 hour <br /> Change in Reading(RF-R,): 0 0 0 <br /> Pass/Fail Threshold or 0 0 0 <br /> Criteria: <br /> Test Result: ❑X Pass ❑Fail N Pass ❑Fail [Z]Pass ❑Fail ❑Pass 0 Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Emergency Return boot failed due to torn test boot.Will return when boot is fixed to test. <br />