Laserfiche WebLink
SWRCB,January 2002 Page 5 of 5 <br /> 8.FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> Fill Sump#Fill Fill Sump# Fill Sump# Fill Sump# <br /> UE058UO02 <br /> Sump Diameter: 38" <br /> Sump Depth: 45" <br /> Height from Tank Top to Top of NA <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 26" <br /> Electrical Penetration: <br /> Condition of sump prior to testing- Good <br /> Portion of Sump Tested: 2"above highest <br /> Sump Material: Fiberglass <br /> Wait time between applying 15 min <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 9:36 am 9:54 am <br /> Initial Reading Ri): 3.3445 3.3438 <br /> Test End Time: 9:51 am 10:10 am <br /> Final Reading(Rf): 3.3539 3.3437 <br /> Test Duration: 15 min 15 min <br /> Chane in Reading Rf-Ri : .0006 .0001 <br /> Pass/Fail Threshold or Criteria: .002 <br /> Test Result: ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Is there a sensor in the sump? ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Does the sensor alarm when either ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> product or water is detected? <br /> Was sensor removed for testing? ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was sensor properly replaced and ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> verified functional after testing? _11 III III <br /> Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests <br /> The snesor was reinstalled to the lowest point but not tested. <br />