Laserfiche WebLink
SWRCB, January 2002 Page _5_ of —5- <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps <br />Fill Riser Containment Sumps are Present, but were Not Tested <br />Test Method Developed By: Sump Manufacturer <br />Other (Specify) <br />® Industry Standard Professional Engineer <br />Test Method Used: <br />Pressure <br />Other (Specify) <br />Vacuum ® Hydrostatic <br />Test Equipment Used: INCON TS -STS UNIT <br />Equipment Resolution: N/A <br />Sump Diameter: <br />Fill Sump # <br />DIESEL <br />38" <br />Fill Sump # <br />Fill Sump # <br />Fill Sump # <br />Sum De the <br />45" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />N/A <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />26" <br />Condition of sump prior to <br />testing: <br />GOOD <br />Portion of Sump Tested <br />2" ABOVE <br />TANK/SUMP <br />COLLAR <br />Sump Material: <br />FIBERGLASS <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 MINUTES <br />Test Start Time: <br />10:06 10:22 <br />Initial Reading (Rj): <br />3.8700 3.8200 <br />Test End Time: <br />10:21 10:37 <br />Final Reading (RF): <br />3.8700 3.8707 <br />Test Duration: <br />15 MIN 15 MIN <br />Change in Reading (RF -R,): <br />.0000 .0007 <br />Pass/Fail Threshold or Criteria: <br />.002 .002 <br />Test Result: ' <br />® Pass Fail <br />Pass Fail <br />Pass Fail <br />Pass Fail <br />Is there a sensor in the sump? <br />® Yes No <br />Yes No <br />Yes No <br />Yes No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />® Yes No NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />Was sensor removed for testing? <br />® Yes No NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes No NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />*Fill Sump pass the industry standard hydrostatic test. <br />No repairs are needed at present time. <br />