Laserfiche WebLink
' If the entire depth of the sump is not tested, specify how much was tested. If the answer to gRy of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />SWRCB, January 2002 Page _4_ of —4- <br />6. PIPING SUMP TESTING <br />Test Method Developed By: Sump Manufacturer ® Industry Standard Professional Engineer <br />Other (Specify) <br />Test Method Used: Pressure Vacuum ® Hydrostatic <br />Other (Specify) <br />Test Equipment Used: INCON TS -STS UNIT <br />Equipment Resolution: N/A <br />Sump # DIESEL <br />Sump # <br />Sump # <br />Sump # <br />!Sump Diameter: 38" <br />mp Depth: 42" <br />Sump Material: FIBERGLASS <br />Height from Tank Top to Top of 22" <br />Highest Piping Penetration: <br />Height from Tank Top to Lowest 21" <br />Electrical Penetration: <br />Condition of sump prior to testing: GOOD <br />2" ABOVE SUMPS <br />Portion of Sump Tested' HIGHEST <br />PRODUCT/VENT <br />PENETRATION <br />Does turbine shut down when <br />sump sensor detects liquid (both Yes No ® NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />product and water)?* <br />Turbine shutdown response time N/A <br />Is system programmed for fail-safe Yes No ® NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />shutdown?* <br />Was fail-safe verified to be Yes No ® NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />operational?* <br />Wait time between applying <br />pressure/vacuum/water and starting 15 MINUTES <br />test: <br />Test Start Time: 10:06 10;22 <br />Initial Reading (Ri): 6.3623 6.3621 <br />Test End Time: 10:21 10:37 <br />Final Reading (RF): 6.3620 6.3620 <br />Test Duration: 15 MIN 15 MIN <br />Change in Reading (RF-Ri): -.0003 -.0001 <br />Pass/Fail Threshold or Criteria: .002 .002 <br />Test Result: 0 Pass Fail <br />Pass Fail <br />Pass Fail <br />Pass Fair <br />Was sensor removed for testing? ® Yes No NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />Was sensor properly replaced and ® Yes No NA <br />Yes No NA <br />Yes No NA <br />Yes No NA <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />*Piping Sump passed the industry standard hydrostatic test. No repairs are needed at present time. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to gRy of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />