8. FIL _ SER CONTAINMENT SUMP TEST <br />SUMD Diameter: <br />30 <br />Sum Depth: <br />54 %" <br />Height from Tank Top to <br />N/A <br />Hi hest Pi in Penetration: <br />Height from Tank Top to <br />21n <br />Lowest Electrical Penetration: <br />Condition of sump prior to <br />CLEAN <br />testing: <br />Portion of Sump Tested <br />ABOVE PENETRATION <br />Sump Material: <br />FIBERGLASS <br />Wait time between applying <br />15 MIN <br />pressure/vacuum/water and <br />starting test: <br />Test Start Time: <br />8:10 <br />8:30 <br />Initial Reading (R,): <br />7.920 <br />7.920 <br />Test End Time: <br />8:25 <br />8:45 <br />Final Reading (RF): <br />7.920 <br />7.920 <br />Test Duration: <br />15 MIN <br />15 MIN <br />Chan a in Readin (RF-Ri): <br />0 <br />0 <br />Pas Fail Threshold: <br />.002 <br />Is there a sensor in the sump? YES <br />Does the sensor alarm when YES <br />either product or water is <br />detected? <br />Was sensor removed for YES . <br />testing? <br />Was sensor properly replaced YES <br />after testing? <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />ermit was obtained or the repairs) <br />R.C.U.S.T.COM <br />