Laserfiche WebLink
PLC-5000 Site Controller, LD-2000 and LD-2000 PLC <br /> The flexible pipeline used for the abbreviated testing was 215 feet in length by 1.5 <br /> inches in diameter with a total volume of 19.7 gallons. If the same criteria for <br /> determining maximum line size is applied to the abbreviated flexible pipeline tests, the <br /> system can be used on flexible pipelines up to 430 feet in length by 1.5 inches in <br /> diameter or 39.5 gallons in volume. <br /> Waiting Time After Delivery of Product <br /> A waiting time after delivery of product is not necessary before a valid test can be <br /> conducted. All of the tests were conducted immediately after product circulation <br /> through the pipeline was stopped. <br /> Waiting Time After Product Circulation <br /> A waiting time after product is circulated through the line or after pumping has stopped <br /> is not necessary before conducting a valid test. <br /> Page 19 <br />