6. <br />8. <br />or completely full and the <br />groundwater table is below the <br />tank bottom. <br />c. When the inner tank is partially <br />or completely full and the tank is <br />partially or completely submerged <br />in groundwater. <br />The leak detection performance <br />of the monitoring system shall be <br />tested and verified by a qualified <br />independent consultant to detect <br />leaks as small as 0.10 gallons per <br />hour with a 99.9% probability of <br />detection and less than a 1.3% <br />probability of a false alarm. <br />All monitoring equipment, including <br />FRP reservoirs and electronic controls, <br />shall be U.L. listed or accepted. <br />If hydrostatically monitored, any <br />solution used in the tank annular <br />space shall have U.L. approval for <br />compatibility with the tank and be a <br />contrasting color to the tank surface <br />to facilitate visual inspection of the <br />tank for leaks prior to burial. <br />2.02 Accessories <br />Anchor Accessories <br />EM <br />L� <br />C. <br />34 <br />Anchor Straps - Provide glass fiber - <br />reinforced plastic anchor straps for <br />each tank shown. Number and location <br />of straps shall be as specified by <br />manufacturer. Each strap shall be <br />capable of withstanding a maximum <br />load for each tank diameter as shown. <br />4'm — 4,200 lbs. <br />6's — 18,000 lbs. <br />8'o — 25,000 lbs. <br />10'o — 32,000 lbs. <br />Straps shall be standard as supplied by <br />the tank manufacturer. <br />Certification Plate - Underwriters <br />Laboratory label shall be permanently <br />affixed to each tank. <br />Flanged Manways <br />1. The standard manway is 22" ID. The <br />30" and 36" ID manways are optional <br />One 22" manway is provided with <br />each tank. <br />2. All manways will be furnished <br />complete with U.L. listed gaskets, <br />bolts and covers. <br />3. Location — see standard tank <br />drawings. <br />4. a. 4' diameter tanks and less than <br />550 gallons, the steel manway cover <br />shall have five fittings. For tanks 600 <br />gallon to 1000 gallon the steel man - <br />way cover shall have four fittings. <br />b. 6' diameter tanks 2500 gallon shall <br />have five fittings in the steel manway <br />cover and 3000 gallon to 6000 gallon <br />tank shall have three fittings in the <br />steel manway cover. <br />c. 8' diameter tanks 5000 gallon shall <br />have five fittings in the steel manway <br />cover, 6000 gallon tanks shall have <br />four fittings, and 8000 gallon tanks <br />and greater shall have three fittings. <br />d. 10' diameter tanks 10000 gallons <br />shall have five fittings in the steel <br />manway cover, 12000 gallon shall <br />have four fittings, and 15000 gallon <br />tanks and greater shall have three <br />fittings. <br />The steel manway cover is standard <br />with 4" diameter NPT fittings. 22" <br />manway covers with an even number <br />of fittings will be placed on an 8" <br />radius. Manway covers with an odd <br />number of fittings will have one fitting <br />centered and the reamining fittings <br />placed on an 8" radius. 30" manway <br />cover fittings are standard 12" radius. <br />36" manway cover fittings are stan- <br />dard 15" radius. <br />5. Manway risers 48" in diameter and <br />42" high will be supplied to provide <br />access to the manway lid. A 24" x 24" <br />galvanized street box with a cover <br />must be provided by contractor for <br />at grade installation. <br />6. Fiberglass manway extension tubes <br />24" long will be provided for the man - <br />ways as outlined in Section 3 above. <br />D. Fill Tubes - Fill tubes of appropriate <br />design will be supplied by contractor. <br />E. Hydrostatic Monitor Accessories <br />1. Brine Antifreeze <br />Brine Solution Designation: BAS -30 <br />Chemical Composition: 30%+ calcium <br />chloride, 1 % to 3% potassium chloride, <br />1% to 2% sodium chloride, Balance water <br />Visual Appearance: <br />Green in color, Odorless fluid <br />Specific Gravity @ 60°F: 1.272-1.317 <br />Factory installed on tanks 30,000 gallon and <br />under. Bulk brine jobsite installed on 35,000 <br />gallon and 40,000 gallon tanks. <br />2. Reservoir Sensor - The FHRB 810 <br />reservoir sensor is specifically <br />designed for installation in the <br />reservoirs of FCI double wall tanks. <br />The components of the sensor are <br />compatible with FCI supplied brine <br />solutions. The sensor is also <br />compatible with any other control <br />panel that accepts normally open or <br />closed switches. The sensor provides <br />two alarm points: high brine and low <br />brine. The sensor can be wired to a <br />control panel to provide only a single <br />alarm (not distinguishing between <br />high or low alarms) or it can be wired <br />to report both alarm conditions. <br />3. Electronic Controllers for <br />Reservoir Sensor - The FHRB 810 <br />reservoir sensor interfaces with the <br />following FCI leak control panels: <br />CPF 1, 2, 3 and 4; or inventory <br />panels: CPI IH and CPI 4. The FCI <br />control panels and reservoir sensor <br />shall be U.L. or Factory Mutual listed <br />as intrinsically safe. The correct <br />number of input circuits must be <br />used, either one or two, to provide <br />the type of desired alarm reporting, <br />i.e. single alarm or dual alarm (high <br />brine or low brine). Additional leak <br />detection sensors and inventory <br />monitoring probes shall be available <br />to interface to the control panels. <br />All control panels shall include: <br />• Alarm lights for each circuit <br />• Audible Alarm with Reset Button <br />• System test button <br />• NEMA 4 Housing <br />• Wall Mounting Capabilities <br />• Dry Contact Relay for each <br />input circuit <br />• RS 232 port (Inventory Panels) <br />• ALPHA numeric display <br />(Inventory Panels) <br />• Printer Option (Inventory Panels) <br />Note: All wiring materials are provided <br />by the contractor. Wiring is required <br />from the power source to the control <br />panel and from the control panel to <br />the probe and sensor assemblies. <br />4. Tank Gauge Probe - The IPFW <br />Series tank gauge probe shall be <br />capable of continuously monitoring <br />liquid levels and detecting water in <br />hydrocarbons at the bottom of tanks. <br />The probe shall be compatible <br />with the liquid it is intended to be <br />submerged in and sized properly to <br />fit into the tank without damaging the <br />tank during installation or operation. <br />The tank gauge probe shall not be <br />rigidly mounted in the tank. <br />Non -Sealed FRP Turbine Enclosure <br />(Model NTE Series) - The non -sealed <br />turbine enclosure consists of a fiberglass <br />reinforced plastic (FRP) enclosure body <br />(variable length in 12" increments, 42" <br />or 48" ID's), an FRP reducer (42"x30" or <br />48"x30" ID's), and a loose fit FRP lid with <br />handle. The reducer opening must be <br />large enough (minimum 28") to allow for <br />the removal of a 22" manway lid. The lid <br />OD must be small enough to be removed <br />through a 36" street box. The enclosure <br />body must be capable of joining to <br />the 42" or 48" diameter secondary <br />containment collar with a leaktight <br />adhesive joint. Cut lines for field trimming <br />will be marked on the bottom 12" of the <br />enclosure body in 3" increments. <br />Model No. Length Model No. Length <br />NTE42-2 2' NTE48-2 2' <br />NTE42-3 3' NTE48-3 3' <br />NTE42-4 4' NTE48-4 4' <br />NTE42-5 5' NTE48-5 5' <br />NTE42-6 6' NTE48-6 6' <br />If needed, refer to Section H for the <br />optional adhesive kit (to bond the <br />enclosure body to the containment <br />collar) and Sections K, L, M and N <br />for the field installed fitting kits (for <br />electrical and plumbing connections <br />to the turbine enclosure). <br />G. Watertight Turbine Enclosure (Model <br />WTE Series) - The watertight turbine <br />enclosure consists of a fiberglass rein- <br />forced plastic (FRP) enclosure body <br />(variable length in 12" increments, 42" <br />or 48" ID's), an FRP reducer (42"x30" <br />or 48"x30" ID's) with o -ring groove and <br />o -ring gasket, and a push on FRP lid with <br />2 handles. The reducer opening must be <br />large enough (minimum 28") to allow for <br />C7 <br />