Laserfiche WebLink
09/1112012 11:57 (209)465-4988 MaryAnn Henderson Page 313 <br /> 0 <br /> SWRCB,January 2002 Page_of <br /> 6. PIPINGS TESTING <br /> Test Method Developed By: 0 Sump Manufacturer X Industry Standard 0 Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used:INCON TS.STS Equipment Resolution:0001" <br /> Sump# EMENNEEM �� <br /> Diesel Sump#Premium Sump#Regular Sump# <br /> Sump Diameter 37" 3711 <br /> Sump Depth: 34" 34" <br /> Sump Material: FIBERGLASS FIBERGLASS <br /> Height from Tank Top to Top of 2110 22" <br /> Highest PiRing Penetration: <br /> Height from Tank Top to Lowest 131f 101, <br /> Electrical Penetration: <br /> Condition of sump prior to testing: GOOD CLEAN <br /> Portion of Sump Tested' 2411 241f <br /> Does turbine shut down when <br /> sump sensor detects liquid(both 0 Yes DNo DNA DYes oNo [INA OYes ONo DNA 11 Yes 0 N DNA <br /> product and water)?* <br /> Turbine shutdown response time <br /> is system programmed for fail-safe DYes 0 N [INA OYes 0 N DNA OYes ONo DNA 0 Yes ONo DNA <br /> shutdown?* <br /> Was fail-safe verified to be D Yes 0 No 0 NA OYes ONo DNA DYes ONo DNA 0 Yes 0 N DNA <br /> operational?* <br /> Waft time between applying <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 1309 1309 <br /> Initial Reading(P4): 4.5995 4.1579 <br /> Test End Time: 1324 1324 <br /> Final Reading(RF): 4.6004 4.1561 <br /> Test Duration: 15 MIN 15 MIN <br /> Change in Reading(RF-R,): .0009 .0018 <br /> Pass/Fail Threshold or Criteria: .002 .002 <br /> Test Result X Pass 0 Fail X Pass 0 Fail OPUS 0 Fail 0 Pus 0 Fail <br /> Was sensor removed for testing? X Yes 0 No 0 NA X Yes 0 No 0 NA 0 Yes 0 No 0 NA DYes 0 N DNA <br /> Was sensor properly replaced and X Yes 0 No D NA XYes 0 N DNA DYes ONo DNA 0 Yes 0 No 0 NA <br /> verified functional after testi g? <br /> !Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Regular STP-Sump not tested. Ave — M 5ema—whogy- aloolr_ U/Vlftz&- <br /> YU C M elellvrft . <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />