Laserfiche WebLink
"r <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K #30224 <br /> Tank #: 1 Test Date: 5/18/97 <br /> Product: Unleaded Regular Work 4: 2201416 <br /> Test Method: Vacutect Test Method: TLDT <br /> Capacity: 11684 Manufacturer: Vaporless <br /> Diameter(in): 92 L/D Model: LD2000 <br /> Product Level(in): 53 L/D Serial#: 9330 <br /> Liquid Volume(Gals): 6921 Line Drain Back(ml): 140 <br /> Liquid Percent(%): 59.2% L/D Trip Time(sec): I <br /> Specific Gravity: 0.750 Holding Pressure(psi): 24 <br /> Coef.of Expansion: 0.000655 Metering Pressure(psi): 10 <br /> Water On Tank(in): 61 L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): -0.8 <br /> Test Start Time: 10:55 PM <br /> Test End Time: 12:32 AM Test Method: TLD-1 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:07 PM <br /> Line End Time: 10:37 PM <br /> Test Method: ULLAGE <br /> Line Start Level: 50 <br /> UllageVolume(gals.): 4763 <br /> Line End Level: 50 - <br /> Ullage Test Time: 10:55 PM <br /> Ullage Vacuum(psi): 1.6 Line Test Rate(gph): 0.000 <br /> Line Test Result: PASS <br /> Ullage Result: PASS <br /> 2 <br />